Plasterboard fire ratings on new-build homes in England

A sheet of plasterboard has no fire rating in minutes on its own. The 30 or 60 minutes belong to a tested wall, floor or ceiling. JMC Drywall Ltd, a dry lining contractor in Tiptree, Essex, explains how the ratings work for site managers and buyers on new-build housing in England.

By JMC Drywall Ltd. Last updated .

What does a plasterboard fire rating mean

A fire rating in minutes belongs to a tested element, never to a loose board. It depends on the board type and thickness, the number of layers, the studs or joists, the screws, the insulation and the jointing. BS EN 520, the product standard for plasterboard, lists fire resistance among the characteristics linked to systems assembled with plasterboards.

Two different properties both get called a fire rating. Reaction to fire describes how much the board itself adds to a fire, and is given as a Euroclass such as A2-s1, d0. Fire resistance is how long a whole wall, floor or ceiling holds back a fire in a standard test, and is given in minutes.

Approved Document B measures fire resistance on three criteria. R is loadbearing capacity. E is integrity, which stops flames and hot gases getting through. I is insulation, which limits the heat reaching the far side. The minutes are time elapsed in a standard test and should not be read as real time.

Reaction to fire: what A2-s1, d0 on a board tells you

A2-s1, d0 is a reaction to fire class under BS EN 13501-1. Classes run from A1, the best, down to F. The s figure grades smoke production from s1, the lowest, to s3. The d figure grades flaming droplets from d0, the lowest, to d2.

The class describes how the surface behaves in a fire. It says nothing about how long a wall lasts. Siniat declares A2-s1, d0 for both its GTEC Standard Board and its GTEC Fire Board, so the Euroclass alone will not tell a fire board from a standard one.

For wall and ceiling linings in a dwelling, Table 4.1 of Approved Document B Volume 1 asks for class C-s3, d2 in most rooms and D-s3, d2 in small rooms of up to 4 square metres. An A2-s1, d0 board meets both.

What is Type F fire rated plasterboard

Type F is the BS EN 520 designation for gypsum plasterboard with improved core cohesion at high temperature. In plain words, the core holds together for longer once the gypsum is heated. Siniat describes the core of its GTEC Fire Board as gypsum with fillers and fibres.

BS EN 520 sets several types, and one board can carry more than one letter. Siniat declares its GTEC Fire Board as Type D and F, and its GTEC Standard Board as Type A.

  • Type A: the letter Siniat declares for its general purpose standard board
  • Type D: controlled density
  • Type E: sheathing board
  • Type F: improved core cohesion at high temperature
  • Types H1, H2 and H3: reduced water absorption
  • Type I: enhanced surface hardness

12.5mm and 15mm plasterboard fire ratings in tested partitions

In Siniat's published partition data, one layer of 12.5mm Siniat Fire MR Board each side of a Siniat CS50 C stud is classified EI 30. One layer of 15mm Siniat Fire Board each side of the same stud is classified EI 60. Those results belong to the whole partition.

The same tables show why the system counts for more than the label on the board. Two layers of 12.5mm Siniat Standard Board, a Type A board, each side of that stud are also classified EI 60.

Siniat states that its figures apply to imperforate, jointed partitions built with its own studs, tracks, boards, screws and finishing products, installed to its guides, and that any alteration may impair them. A result for one manufacturer's system does not carry across to another manufacturer's board or stud.

Examples from the Siniat Drywall Manual, Partitions, version 2.2.0, July 2025. Single frame, studs at 600mm centres, no insulation
Siniat systemBoards each sideStudFire classification
CS50R-12StOne layer of 12.5mm Siniat Standard BoardCS50/Rx30 minutes to BS 476-22
CS50R-12FMROne layer of 12.5mm Siniat Fire MR BoardCS50/RxEI 30 to EN 13501-2
CS50R-15FOne layer of 15mm Siniat Fire BoardCS50/RxEI 60 to EN 13501-2
CS50R-212StTwo layers of 12.5mm Siniat Standard BoardCS50/RxEI 60 to EN 13501-2

Where a new-build home needs 30 or 60 minute fire resistance

Approved Document B Volume 1 covers dwellings in England. In a new-build house it asks for fire resisting construction around a protected stair, between an integral garage and the house, in walls between houses, and in the structure. Most of these are set at 30 minutes, with 60 minutes for walls between houses.

These are the guidance values. The fire strategy and specification for your scheme set what is built, and the manufacturer's tested detail sets how it is built. The rules differ in Scotland, Wales and Northern Ireland, and this guide covers England only.

The current edition on gov.uk is the 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments, collated with the 2029 amendments.

  • Protected stair: REI 30 at all storeys where a house has a storey more than 4.5m above ground, with cavity barriers or an EI 30 ceiling above it (paragraph 2.5)
  • Integral or attached garage: REI 30 from the garage side to the wall and any floor between garage and house, and an E 30 Sa self-closing door (paragraph 5.6 and Diagram 5.1)
  • Semi-detached and terraced houses: every wall between the houses built as a compartment wall (paragraph 5.5), with a minimum of 60 minutes (Table B2)
  • Structure, including floors: 30 minutes where the top floor is up to 5m above ground, and a minimum of 30 minutes in three storey houses (Table B2)
  • Flats: every floor between flats and every wall separating a flat from another part of the building is a compartment floor or wall (paragraph 7.1)

What stops a fire rated partition performing on site

A fire rated partition performs as tested only when it is built as tested. Approved Document B warns that small differences in fixing method, joints, dimensions, insulation and air gaps can significantly affect fire performance. On a housing site the faults that defeat a lining are usually simple ones.

Siniat's manual asks for services to be planned so that penetrations through rated partitions are kept to a minimum. It allows pipes of 40mm internal diameter or less to be sealed with its intumescent acoustic sealant, apart from cPVC pipes, and refers other openings to the fire stopping product supplier for installation and tested details.

  • Standard board fixed where the specification calls for fire board, often from a mixed stack
  • Screws at wider centres than the system allows. Siniat's single frame partitions call for 300mm
  • A second layer left off, or joints not staggered between layers
  • Pipes and cables through the wall left open, or sealed with an untested product
  • Back boxes cut into a rated wall with no tested detail behind them
  • Joints left unfilled where the system was tested jointed

BS 476 or BS EN 13501: which classification applies

Approved Document B gives fire resistance as European classes under BS EN 13501-2, and allows BS 476 results as an alternative for products lawfully on the market. The 2029 amendments remove that alternative from 2 September 2029. Approved Document B notes that the national and European classifications do not automatically equate.

The national classes for reaction to fire went first. The 2025 amendments removed them from 2 March 2025, and dropped BS 476 parts 6 and 7 from the document's list of standards.

Transition rules apply. The earlier guidance still applies where a building notice, initial notice or full plans application was made before 2 September 2029 and the work is sufficiently progressed, which for a new building means foundations or piling started, before that day or within six months of it.

Questions

What buyers ask us

Who decides which fire rated plasterboard system goes on a new-build scheme?
The designer does, through the fire strategy and the specification, and building control checks the design. The dry liner builds the manufacturer's tested system as specified. JMC Drywall Ltd is on the installer registers of British Gypsum and Knauf. Where a drawing, the specification and the tested detail disagree, the question belongs with the designer before any board goes up.
What is the fire rating of 12.5mm plasterboard?
12.5mm plasterboard has no fire rating of its own. Its minutes come from the system it is part of. In Siniat's published data, one layer of 12.5mm Siniat Fire MR Board each side of a CS50 C stud is classified EI 30. One layer of 12.5mm Siniat Standard Board each side of the same stud gives 30 minutes when tested to BS 476-22.
What is the fire rating of 15mm plasterboard?
15mm plasterboard has no rating in minutes until it is part of a tested system. Siniat's CS50R-15F partition, with one layer of 15mm Siniat Fire Board each side of a CS50 C stud at 600mm centres, is classified EI 60 to EN 13501-2. Change the stud, the screws or the board maker and that classification no longer applies without other evidence.
Is pink plasterboard always fire rated?
No. Colour is a maker's convention and carries no classification. Siniat's GTEC Fire Board is pink on the front, and its data sheet declares it Type D and F to BS EN 520. The reliable check is the product name and batch printed on the back and long edges, matched against the board named in the tested system.
Does fire rated plasterboard need special screws or sealant?
It needs the screws and sealants named in the tested system. Siniat's single frame partitions call for boards fixed to the studs at 300mm centres with its drywall screws. Pipes of 40mm internal diameter or less through a rated wall may be sealed with its intumescent acoustic sealant. For other openings it points to a proprietary fire stopping product and that supplier's tested detail.
When does BS 476 stop being accepted for fire resistance in England?
The 2029 amendments to Approved Document B remove the BS 476 alternative for fire resistance from 2 September 2029. Work notified to building control before that date, and sufficiently progressed before it or within six months after it, may still follow the earlier guidance. A classification to BS EN 13501-2 is the route Approved Document B gives in both versions.